🔴 PEX Expansion Calculator
Calculate Thermal Expansion & Support Spacing
🔴 PEX Thermal Expansion Fundamentals
PEX (cross-linked polyethylene) pipe expands and contracts significantly more than metal pipes when temperature changes. Proper installation requires accounting for this movement.
Expansion Formula
Expansion (inches) = Length (ft) × [ΔT (°F) / 10°F] × 1.1
Example: 100-foot run, 80°F temperature increase: 100 × (80/10) × 1.1 = 8.8 inches
Support Spacing Requirements
| Pipe Size | Horizontal Support Spacing | Vertical Support Spacing |
|---|---|---|
| 1/2" | 32 inches | 48 inches |
| 3/4" | 36 inches | 60 inches |
| 1" | 48 inches | 72 inches |
| 1-1/4" to 2" | 60 inches | 84 inches |
Note: For hot water lines (140°F+), reduce spacing by 25-30% to control expansion movement.
Expansion Compensation Methods
- Expansion Loops: Create a U-bend or offset in the run (minimum 12" offset for 50+ ft runs)
- Flexible Supports: Use sliding clips instead of rigid straps at one end
- Direction Changes: Natural bends at 90° elbows absorb some movement
- Expansion Joints: For runs over 100 feet, install dedicated expansion compensators
"The worst PEX failure I see is when DIYers rigidly strap a 50-foot hot water run at both ends with no slack. When that pipe heats up, it has nowhere to go—it either buckles off the wall or cracks at a fitting. ALWAYS leave the last 2-3 feet 'floating' with a sliding support, or add an offset. Also, when installing in winter (30°F), that same pipe will shrink 4+ inches when it warms to 140°F in summer. Plan for movement in both directions!"
⚠️ Common Mistakes
1. Rigid End-to-End Installation: Never strap PEX tightly at both ends of a long run. The pipe MUST have freedom to move. Use a slip joint or offset.
2. Ignoring Installation Temperature: If you install PEX at 20°F in winter, and it operates at 140°F, that's a 120°F delta = massive expansion. Always note the installation temp.
3. Undersupporting Hot Runs: Cold water lines can use wider spacing, but hot water PEX sags significantly. Support every 24-30 inches for 140°F+ water.