⚡ Conduit Fill Calculator (NEC 2020)

Calculate maximum wire capacity per NEC code

Most common: THHN

📊 Quick Reference: EMT Conduit Fill (THHN Wire)

Wire Size Maximum Wires per Conduit Size
1/2" 3/4" 1" 1-1/4" 2"
10 AWG 5 10 16 28 51
8 AWG 3 6 9 16 29
6 AWG 1 4 6 10 19

Source: NEC 2020 Annex C, Table C1. For reference only—verify with official NEC tables for your specific application.

💡 From Marcus Rodriguez, Master Electrician (23 years, NEC instructor):

"I've seen apprentices fail inspections because they crammed too many wires in conduit. The 40% rule isn't a suggestion—it's code. And here's what they don't teach in school: those NEC tables assume you're pulling THHN in a straight run. Add two 90-degree bends and you better stay well under 40% or you'll never pull those wires without damaging insulation. I personally never exceed 35% on runs with multiple bends. Also, inspectors carry wire gauges—they will measure your conduit fill. Don't try to fudge the numbers."

📐 Understanding NEC Fill Calculations

The National Electrical Code (NEC) strictly regulates conduit fill to prevent overheating and ensure wires can be safely pulled and removed.

NEC Chapter 9, Table 1 Fill Percentages

  • 1 conductor: 53% fill maximum
  • 2 conductors: 31% fill maximum
  • 3+ conductors: 40% fill maximum (most common scenario)

These percentages apply to the conductor cross-sectional area including insulation, not the bare copper.

How to Calculate Manually

Step 1: Find conduit internal area from NEC Chapter 9, Table 4

Example: 3/4" EMT = 0.213 square inches

Step 2: Calculate 40% fill allowance

0.213 × 0.40 = 0.0852 square inches available

Step 3: Find wire area from NEC Chapter 9, Table 5

12 AWG THHN = 0.0133 square inches per wire

Step 4: Divide available space by wire area

0.0852 ÷ 0.0133 = 6.4 wires, round down to 6 wires maximum

Note: NEC Annex C tables account for optimized bundling and allow slightly more—always cross-reference with Annex C for final verification.

⚠️ Common Mistakes

1. Not counting ground wires: Ground conductors count toward fill. A 12/2 with ground cable = 3 wires for fill purposes.

2. Exceeding 40% thinking "close enough": Inspectors have no tolerance. 41% fill = failed inspection, rework required.

3. Using wrong conduit type tables: EMT, PVC Schedule 40, and Rigid all have different internal areas. Using EMT table for PVC = wrong answer.

4. Ignoring bend radius and pulling difficulty: Code-compliant doesn't mean easy to pull. Multiple bends with 40% fill = damaged wire insulation.

❓ FAQ

What is the 40% conduit fill rule?

NEC Chapter 9, Table 1 limits fill to 40% of conduit area when running 3+ wires. This prevents overheating and eases wire pulling.

How many 12 AWG in 3/4" EMT?

Maximum 16 THHN 12 AWG wires per NEC Annex C, Table C1.

Do grounds count for fill?

Yes, equipment grounding conductors count at their actual size toward total fill.

Can I mix wire sizes?

Yes. Calculate each wire's area, sum the total, and verify it doesn't exceed 40% of conduit area.

MR

Marcus Rodriguez

Master Electrician, 23 years experience, NEC Instructor

📌 Embed This Tool

<iframe src="https://calcs.top/other/conduit-fill-calculator/" width="100%" height="800" frameborder="0"></iframe>