⚡ Conduit Fill Calculator (NEC 2020)
Calculate maximum wire capacity per NEC code
📊 Quick Reference: EMT Conduit Fill (THHN Wire)
| Wire Size | Maximum Wires per Conduit Size | ||||
|---|---|---|---|---|---|
| 1/2" | 3/4" | 1" | 1-1/4" | 2" | |
| 14 AWG | 12 | 22 | 35 | 61 | 111 |
| 12 AWG | 9 | 16 | 26 | 44 | 80 |
| 10 AWG | 5 | 10 | 16 | 28 | 51 |
| 8 AWG | 3 | 6 | 9 | 16 | 29 |
| 6 AWG | 1 | 4 | 6 | 10 | 19 |
Source: NEC 2020 Annex C, Table C1. For reference only—verify with official NEC tables for your specific application.
"I've seen apprentices fail inspections because they crammed too many wires in conduit. The 40% rule isn't a suggestion—it's code. And here's what they don't teach in school: those NEC tables assume you're pulling THHN in a straight run. Add two 90-degree bends and you better stay well under 40% or you'll never pull those wires without damaging insulation. I personally never exceed 35% on runs with multiple bends. Also, inspectors carry wire gauges—they will measure your conduit fill. Don't try to fudge the numbers."
📐 Understanding NEC Fill Calculations
The National Electrical Code (NEC) strictly regulates conduit fill to prevent overheating and ensure wires can be safely pulled and removed.
NEC Chapter 9, Table 1 Fill Percentages
- 1 conductor: 53% fill maximum
- 2 conductors: 31% fill maximum
- 3+ conductors: 40% fill maximum (most common scenario)
These percentages apply to the conductor cross-sectional area including insulation, not the bare copper.
How to Calculate Manually
Step 1: Find conduit internal area from NEC Chapter 9, Table 4
Example: 3/4" EMT = 0.213 square inches
Step 2: Calculate 40% fill allowance
0.213 × 0.40 = 0.0852 square inches available
Step 3: Find wire area from NEC Chapter 9, Table 5
12 AWG THHN = 0.0133 square inches per wire
Step 4: Divide available space by wire area
0.0852 ÷ 0.0133 = 6.4 wires, round down to 6 wires maximum
Note: NEC Annex C tables account for optimized bundling and allow slightly more—always cross-reference with Annex C for final verification.
⚠️ Common Mistakes
1. Not counting ground wires: Ground conductors count toward fill. A 12/2 with ground cable = 3 wires for fill purposes.
2. Exceeding 40% thinking "close enough": Inspectors have no tolerance. 41% fill = failed inspection, rework required.
3. Using wrong conduit type tables: EMT, PVC Schedule 40, and Rigid all have different internal areas. Using EMT table for PVC = wrong answer.
4. Ignoring bend radius and pulling difficulty: Code-compliant doesn't mean easy to pull. Multiple bends with 40% fill = damaged wire insulation.
❓ FAQ
What is the 40% conduit fill rule?
NEC Chapter 9, Table 1 limits fill to 40% of conduit area when running 3+ wires. This prevents overheating and eases wire pulling.
How many 12 AWG in 3/4" EMT?
Maximum 16 THHN 12 AWG wires per NEC Annex C, Table C1.
Do grounds count for fill?
Yes, equipment grounding conductors count at their actual size toward total fill.
Can I mix wire sizes?
Yes. Calculate each wire's area, sum the total, and verify it doesn't exceed 40% of conduit area.
Marcus Rodriguez
Master Electrician, 23 years experience, NEC Instructor