💨 Airflow CFM Calculator

Calculate CFM from Velocity (FPM) and Area

1.0 = Open Duct, 0.75 = Standard Register
Enter one average reading or multiple points to average automatically.

📐 How to Calculate Airflow (CFM)

Airflow is calculated using the formula Q = V × A, where:

  • Q = Airflow in CFM (Cubic Feet per Minute)
  • V = Velocity in FPM (Feet per Minute)
  • A = Area in Square Feet

The Importance of Ak Factor

If you are measuring airflow at a grille or register, you cannot use the simple physical area (Width × Height). The metal vanes block some of the air. The Ak Factor (or Effective Area) accounts for this blockage.

  • Open Duct: Ak = 1.0
  • Commercial Grille: Ak ≈ 0.80 - 0.90
  • Residential Stamped Register: Ak ≈ 0.65 - 0.75

Always check the manufacturer's engineering data for the exact Ak factor if available.

💡 From Jeff Martinez, HVAC Technician (18 years):

"When using a vane anemometer on a supply register, don't just hold it in the center! The air moves fastest in the center and slower at the edges. I use a 'snake' pattern to traverse the entire face of the grille over 10-15 seconds to get a true average. If you only measure the 'hot spot,' you'll overestimate your CFM by 20% or more."

⚠️ Common Mistakes

1. Forgetting to convert to Square Feet: Velocity is in Feet/Min, so Area must be in Square Feet. If you use Square Inches, you must divide by 144. (This calculator does it for you!)

2. Ignoring the Ak Factor: Measuring a 12x12 register (1 sq ft) at 500 FPM does NOT mean 500 CFM. With an Ak of 0.75, it's actually 375 CFM.

3. Measuring too close to a bend: Turbulence destroys accuracy. Try to measure in a straight section of duct if possible, or take more readings to average out the turbulence.

❓ FAQ

What is a good CFM for a bedroom?

A typical bedroom needs about 1 CFM per square foot for cooling. A 12x12 room (144 sq ft) usually needs 100-150 CFM depending on windows and sun exposure.

Can I use an anemometer app on my phone?

No. Phone microphones cannot accurately measure air velocity. You need a dedicated anemometer (hot wire or vane type) for meaningful results.

Reviewed by Jeff Martinez
Licensed HVAC Technician, 18 years experience in residential and light commercial air balancing.